Logged Data* 
The previous 128 days of data are accessible with the MATE. The data is logged each night at 
midnight. Be sure the MATE’s clock is set to the correct local time (refer to your MATE manual).
* Data Logging
User Adjustable Set Points
•  Battery charge factor (65-100%) [see page 29]
•  Battery bank capacity 0-10000 amp hours
•  Shunt A, B, C—enabled or disabled
•  Absorb volts (0-80.0 volts, the maximum voltage the battery can absorb)
•  Return amps (0-500.0A, the maximum current amperage going into the battery)
•  Parameters met timer (0-240 minutes, the amount of time allowed to recharge)
•  AUX Relay Set Points
 
 
    
 
 
  Manual-On, 
Auto, 
Manual-Off —allows the user to turn the Aux Relay on and  
 
 
off  like a manual switch or to set it to Auto and have it function when certain  
  conditions 
are 
met
 
 
Volts HI—when user determined high voltage value is met, the Aux activates
 
 
Volts LO—the Aux activates when a low voltage value is met
 
 
SOC (State-of-Charge) HI—a high state-of-charge activates the Aux
 
 
SOC  (State-of-Charge) LO—a low state-of-charge activates the Aux
 
 
HI Delay—the user can adjust the high set point delay time (in minutes)
 
 
LO Delay—the user can adjust the low set point delay time (in minutes)
 
 
  
 
 
AUX-INVERT LOGIC—the invert logic function can be activated with a YES or  
 
 
NO command (see page 16)