Справочник Пользователя для MGE UPS Systems EX RT CLA

Скачать
Страница из 6
CLA Module (Long backup time charger) 
(Part number 86004)
Extended back-up time (up to 8 hours at full load) requires a high power battery cabinet connected to the EX
5/7/11RT via the CLA module.
IMPORTANT
The CLA can not be used to charge the battery module (EXB). It is designed to charge the
customer provided high power battery cabinet.
Battery backup time chart.
Battery Backup Time
Recommended Batteries 
EX  5 RT
EX  7 RT
EX  11 RT
2 hours
50 Ah
65 Ah
100 Ah
4 hours
100 Ah
130 Ah
200 Ah
8 hours
200 Ah
200 Ah
400 Ah
Total battery voltage : 240 V DC (20 x 12V DC).
The battery capacity must be set within the UPS (5 Ah increment possible, see UPS Personalization sect
STEP 1   EX RT CLA Module Unpacking and Parts Check
EX RT CLA Module
EX RT CLA Module Installation
2
86-86000-04 AO
EX RT CLA Module
Installation and 
User Manual
Power Cable
EX  RT  CLA Module Box Contents
Tower Stand Expanders
Battery Detection Cable
Stabilizer Bracket
(4 screws included)