Справочник Пользователя для IBM UPS 10000XHV

Скачать
Страница из 29
14
 
 3:  U
SER 
C
ONFIGURABLE 
I
TEMS
 
N
OTE
:
 
S
ETTINGS ARE MADE THROUGH THE SUPPLIED 
P
OWER
C
HUTE 
B
USINESS 
E
DITION SOFTWARE
,
 
N
ETWORK 
M
ANAGEMENT 
C
ARD
,
 OR TERMINAL MODE
.
 
R
EFER TO THE SOFTWARE HELP GUIDES FOR DETAILS
. 
F
UNCTION
 
F
ACTORY
 
D
EFAULT
 
U
SER 
S
ELECTABLE 
C
HOICES
 
D
ESCRIPTION
 
Automatic Self-Test 
Every 14 days  
(336 hours) 
Every 7 days 
(168 hours), 
Every 14 days 
(336 hours), 
On Startup Only,  
No Self-Test 
This function sets the interval at which 
the uninterruptible power supply will 
execute a self-test.  
Uninterruptible 
Power Supply ID 
UPS_IDEN 
Up to eight characters  Use this field to uniquely identify the 
uninterruptible power supply, (i.e. 
server name or location) for network 
management purposes. 
Date of Last Battery  
Replacement 
Manufacture Date 
mm/dd/yy 
Reset this date when you replace the 
battery modules. 
Minimum Capacity 
Before Return from 
Shutdown 
0 percent 
0, 15, 25, 35, 50, 60, 
75, 90 percent 
The uninterruptible power supply will 
charge its batteries to the specified 
percentage before it powers up con-
nected equipment, following a low-
battery shutdown. 
Alarm Delay After 
Line Failure 
5 second delay 
5 second delay, 
30 second delay, 
At Low Battery, 
Never 
The user can mute an ongoing alarm or 
disable all existing alarms permanently. 
Shutdown Delay 
20 seconds 
0, 20, 60, 120, 240, 
480, 720, 960 sec-
onds 
The interval is set between the times 
when the uninterruptible power supply 
receives a shutdown command and 
actual shutdown. 
Duration of Low 
Battery Warning 
2 minutes 
(PowerChute soft-
ware provides 
automatic, unat-
tended shutdown 
when approxi-
mately two min-
utes of battery 
runtime remain.) 
2, 5, 7, 10, 12, 15, 18, 
20 minutes 
The low battery warning beeps become 
continuous when two minutes of run-
time remain. 
Change the warning interval to a higher 
setting if the operating system requires 
a longer interval for shutdown. 
Synchronized Turn-
on Delay 
0 seconds 
0, 20, 60, 120, 240, 
480, 720, 960 sec-
onds 
The uninterruptible power supply will 
wait the specified time after the return 
of utility power before turn-on (to 
avoid branch circuit overload).  
High Bypass Point 
+10% of output 
voltage setting 
+5%, +10%, +15%, 
+20% 
The uninterruptible power supply will 
pass this maximum voltage to con-
nected equipment during internal by-
pass operation. 
Low Bypass Point 
-30% of output 
voltage setting 
-15%, -20%, -25%,  
-30% 
The uninterruptible power supply will 
pass this minimum voltage to con-
nected equipment during internal by-
pass operation. 
Output Voltage 
230 Vac 
200, 208, 220, 230, 
240 Vac 
The user is able to select the uninter-
ruptible power supply output voltage 
while online. Use the voltage setting 
applicable to your region.