Positioning the Uninterruptible Power Supply 
 
32–55 kg  
(70–120 lb)
 
Attention: The uninterruptible power supply will remain heavy without the battery modules. Select a location 
sturdy enough to handle the weight. 
Do not operate the uninterruptible power supply in excessive dust or in temperature and humidity conditions outside the speci-
fied limits. 
Make sure that the air vents on the front and rear of the uninterruptible power supply are not blocked.  
Placement of the unit should correspond with the following graphical depiction. 
 
Hardwiring the Uninterruptible Power Supply 
Attention: Wiring must be performed by a qualified electrician. 
1.  Install a utility circuit breaker according to local electrical codes (see tables below) for input wiring. 
200/208 V Applications 
Input Connection 
Output Connection (Optional) 
Single-Phase: Wire to L1, N, and 
Wire to L1A, N1, and 
 
System Wiring 
Voltage 
Current 
Full Load 
(Nominal) 
External  
Circuit Breaker 
(typical) 
Wire Size 
(typical) 
Input  
200/208 V 
38 amps 
50 amps / 2-pole 
10 mm
2
 
UPS 7500XHV 
Output 
200/208 V 
38 amps 
(as needed) 
10 mm
2
 
Input  
200/208 V 
50 amps 
63 or 70 amps / 2-
pole 
16 mm
2
 
UPS 10000XHV 
 
Output 
200/208 V 
50 amps 
(as needed) 
16 mm
2
 
 
220/230/240 V Applications 
Input Connection 
Output Connection (Optional) 
Single-Phase: Wire to L1, N, and 
Three-Phase: Wire to L1, L2, L3, N, and 
Wire to L1A, N1, and 
 
System Wiring 
Number 
of 
Phases 
Voltage Current 
Full Load 
(Nominal) 
External  
Circuit Breaker 
(typical) 
Wire Size 
(typical) 
Input  
220/230/240 V 
38 amps 
50 amps / 2-pole 
10 mm
2
 
Input 
380/400/415 V 
14 amps/ 
phase when online, 
38 amps on L1 in 
bypass 
50 amps/ 4-pole 
10mm
2
 
UPS 7500XHV 
Output 
220/230/240 V 
38 amps 
(as needed) 
10 mm
2
 
Input  
220/230/240 V 
50 amps 
63 amps / 2-pole 
16 mm
2
 
Input 
380/400/415 V 
18 amps/ phase 
when online, 50 
amps on L1 in 
bypass 
63 amps/ 4-pole 
16 mm
2
 
UPS 10000XHV 
 
Output 
220/230/240 V 
50 amps 
(as needed) 
16 mm