Section 3:  Operation 
From the Set Delays menu, press 3. UNIT RESTART to configure the 
restart delay: 
ENTER RESTART DELAY 
<00.1> XX.X MINUTES 
THEN PUSH ENTER 
PUSH CLEAR TO RETURN 
 
Enter the desired time for the restart delay. The default is 0.1 minutes. 
Press Enter to accept the new delay, then press C to return to the Set 
Delays menu. 
When you have configured the delays, from the Set Delays menu, press 
5 to return to the Set Options Sub-menu. 
3. TEMP/HUM 
From the Set Options Sub-menu, press 3. TEMP/HUM to display the 
Set T/H menu: 
SET T/H MENU 
1.T/H ALARM POINTS 
2.TEMP. STAGING 
3.F/C 4.LOCK  5.EXIT 
 
Set Options Sub-menu (cont’d) 
The Set Temp/Hum and Temp Staging functions apply only to Zone 1. 
The temperature and humidity inputs are from a separate remote sensor, 
not from an operating unit.  
From the Set T/H menu, press 1. T/H ALARM POINTS: 
TEMP HI>75 LOW>65 
HUM HI>60 LOW>40 
<RANGE 50-90> 00=off 
E=NEXT C=RETURN 
 
Beginning with Temp Hi, enter the temperature and humidity alarm 
points. The third line displays the range for the alarm limit you are 
selecting. Press E to continue to the next point. When you have set all 
points, press C to return to the Set T/H menu. 
From the T/H menu, press 2. TEMP. STAGING: 
STAGING ON/OFF 
>OFF 
NORMAL TEMP 
>72 
SENSITIVITY >02 
1=ON O=OFF  E=NEXT 
 
Beginning with Staging ON/OFF, configure each parameter. Press E at 
the last parameter to return to the T/H menu. 
From the T/H menu, press 3. F/C to configure degrees in Fahrenheit or 
Celsius: 
SELECT F/C <F> 
  Liebert RAC2-8 
 11