Section 3:  Operation 
 
Terminal 
A local terminal can be connected directly by an EIA-232 
communication cable to the RAC2-8, or a remote terminal can be 
connected through modems. All of the status information and control 
functions available at the RAC2-8 local display are available from the 
terminal. An additional function available at the terminal is Set Modem.  
The terminal also displays a status message with time and date stamp 
whenever a unit changes status (OFF or ON). These status messages 
will be printed if a printer (instead of a terminal) is connected to the 
EIA-232 port. Once each 24 hours (at midnight) the terminal checks its 
ability to communicate with the RAC2-8 and writes a Comm Check 
message. 
A terminal connected to an active RAC2-8 displays alarm and status 
messages when they occur. The prompt then asks the operator to press 
<space>, <S>, or <A>. 
07-15-96 
12:14:12 
On UNIT 03 FORCED ON 
07-15-96 
12:14:19 
On UNIT 63 RESTORED Menu 
Exited - Press <space> to Enter Menu, <S> for 
Status, <A> for Alarms 
<space> displays Main Menu after a password is entered. 
<S> displays present status.  
<A> displays a list of alarms (up to 20).  
LOG ON: 
 
is the prompt to enter a password. This prompt is also displayed when 
the system is accessed through a modem. 
Main Menu 
The Main Menu is displayed on a terminal as shown below: 
RAC2-8 MAIN MENU 
1. Status 
2. Setup Zones/Units Options Menu 
3. Alarms Review 
4. Alarms Clear 
5. Set Clock 
6. Override a Unit 
7. Set Modem Options 
8. Setup Temp/Humid Options Menu 
9. Setup Standby Unit Options 
A. Display SS Alarm Block 
P. Set New Password 
X. Exit 
Main Menu (cont’d) 
Each Main Menu item has a corresponding screen that lets you 
configure the system parameters. Each screen is shown in the following 
sections. 
When you make a program selection 
from the terminal, the screen is 
displayed again with the new 
value(s). 
 
16 