Справочник Пользователя для Liebert RAC2-8

Скачать
Страница из 47
 
  Liebert RAC2-8 
 1 
 
Section 1:  Introduction 
The Liebert RAC2-8 remotely controls from two to eight environmental 
units. Each unit is assigned to a Zone (room) from 1 to 4. In Zone 1, the 
largest room, the temperature and humidity can be monitored. The 
common alarm output from each unit is monitored and annunciated by 
the RAC2-8. Up to 20 system alarms can be stored with time and date 
stamp. All alarms are latching and must be manually cleared. 
See SECTION 5 — 
INSTALLATION
 for special 
instructions when using the RAC2-8 
with Liebert mini-MATE, mini-MATE 
Plus, and DataMate environmental 
control systems. 
The most important control functions are Autochangeover, 
Autosequencing, and Standby Testing. Each unit can be assigned a 
Running or Standby status. 
Autochangeover turns on a Standby unit if a Running unit in the same 
zone has an alarm. The Running unit (with alarm) will be turned off if 
that control option is selected. Each unit will return to its previous 
status when the alarm is manually cleared. 
Autosequencing balances unit run-times by changing Standby units to 
Running (and Running units to Standby) at programmed time intervals. 
Standby Testing turns on Standby units at programmed intervals to test 
their operation. Note that Autosequencing and Standby Testing cannot 
both be selected at the same time. 
Other control functions include Manual Override, Emergency Power 
Operation, Power Failure Mode, Password, and Programmable Delays.                        
Refer to SECTION 4 — GLOSSARY OF CONTROL FUNCTIONS 
for more details. 
System outputs include Humidity Lockout Relay, Optional Control 
Lockout Relay, and Common Alarm. Communication ports are 
EIA-232 for terminal or printer, a modem port, and a proprietary 
EIA-422 port for communication to a Liebert SiteScan monitoring 
system. 
The RAC2-8 can be operated locally from the built-in control panel or 
remotely from an optional terminal (EIA-232 communication). This 
manual shows examples of several typical display screens during both 
local and remote operation.