Справочник Пользователя для Liebert GXT2-4500RT230

Скачать
Страница из 40
System Description
5
2.5
DC-to-DC Converter
The DC to DC converter utilizes energy from the battery system and raises the DC voltage to the opti-
mum operating voltage for the inverter. This allows the inverter to operate continuously at its opti-
mum efficiency and voltage, thus increasing reliability.
2.6
Battery
The UPStation GXT2 utilizes valve-regulated, nonspillable, lead acid batteries. To maintain battery 
design life, operate the UPS 
in an ambient temperature of 20°C to 25°C (68°F to 77°F). Optional external battery cabinets are 
available to extend battery run times.
2.7
Dynamic Bypass
The UPStation GXT2 provides an alternate path for mains power to the connected load in the 
unlikely event of a UPS malfunction. Should the UPS have an overload, overtemperature, or UPS 
failure condition, the UPS automatically transfers the connected load to bypass. Bypass operation is 
indicated by an audible alarm and illuminated amber Bypass LED (other LEDs may be illuminated to 
indicate the diagnosed problem). To manually transfer the connected load from the inverter to bypass, 
press the Standby button once.
NOTE
The bypass power path does NOT protect the connected equipment from disturbances 
in the mains supply.