Users Manual & Installation Guide  
                            PV- 5127: 
Power supply module with UPS 
 
 
Page 31 of 31 
Differences between PV-5127 and PV-5127A 
The PV-5127 is available in a version without UPS and battery charger.  The ordering code for this 
product is PV-5127A.  These things are different in this version: 
 
 
The mains voltage range is nominally 10-35V instead of 18-35V.  The mains monitor 
reports mains failure at mains voltage below 9.0V and mains OK at above 9.5V, instead of 
16.5V and 17.5V, respectively. 
 
The battery charger is omitted. 
 
The input selector circuit is omitted. 
 
J1 for battery temperature sensor is omitted. 
 
CN3 for “RS232” UPS communication is omitted. 
 
 
Block diagram of the PV-5127A