3.25.4 Connection Instructions : 
Operation result, push, read, pop ... MPS, MRD, MPP
Functions
(1) Stores the operation result (ON/OFF) immediately before itself.
(2) The MPS instruction can be used consecutively up to 12 times.
In the ladder mode, however, it can be used up to 11 times.
When the MPP instruction is used midway, the number of used MPS instructions
is decremented by 1.
(1) Reads the operation result stored by the MPS instruction, and continues
operation from the next step with that operation result.
(1) Reads the operation result stored by the MPS instruction, and continues
operation from the next step with that operation result.
(2) Clears the operation result stored by the MPS instruction.
Usable Devices
Digit 
Desig
nation
Error Flag
Bit devices
Word (16-bit) devices
Constants
Level
X
Y
M
T
C
D
K
H
N
(M9010,M9011)
MPS
MRD
MPP