Справочник Пользователя для Mitsubishi Electronics 700 Series

Скачать
Страница из 183
33
Inverter Status Monitoring, Special Registers
for Control
1
1.7.5
Inverter parameter access error (D9150)
If any value outside the setting range is written during parameter write, set frequency
write, parameter clear, etc. from the sequence program of the inverter, or if write is
performed when write is disabled, a write alarm occurs and the corresponding alarm
code is stored into D9150.
<Parameter>
The parameter No. + H8000 is stored into D9150.
Example: If an error occurs during write of Pr.0 Torque boost, H8000 (H0 + H8000) is
stored into D9150.
If an error occurs during write of Pr.10 DC injection brake operation frequency,
H800A is stored into D9150.
<Operation mode, set frequency, alarm definition batch clear, all parameter
clear>
HFFFF is stored into D9150. (Normal 0)
1.7.6
Inverter status (D9151)
The running status and operating status of the inverter are stored.
The corresponding bits are set according to the inverter status.
Device No.
Name
Data Access Enable 
Condition
D9150
Inverter parameter access error
Always
POINT
If write is completed normally after error occurrence, D9150 is not cleared
(D9150 data is held at error occurrence). When using D9150 to stop operation,
etc., the user must clear it.
Device No.
Name
Data Access Enable 
Condition
D9151
Inverter status
Always
B15
B8B7
B4B3
B0
0:OFF
1:ON
Inverter running(RUN)
Forward running
Reverse running
Up to frequency(SU)
Overload alarm(OL)
Instantaneous power failure
/undervoltage(IPF)
Output frequency 
detection(FU)
Alarm output(ALM)
Minor fault output(LF)