System Configuration
1.3 System Configuration
The following shows the system configuration for use of the PLC function.
<System configuration example>
Communication specifications
Set the following setting in communication parameters of the inverter.
Inverter Parameter
GX Developer Setting
Inverter initial setting
Pr.118 PU communication speed
96 (9600bps)
192 (19200bps)
Pr.119 PU communication stop bit length
0 (data length: 8 bits, stop 
bit: 1 bit)
1 (data length: 8 bits, stop 
bit: 2 bit)
Pr.120 PU communication parity check
1 (with odd parity check)
2 (with even parity check)
Pr.122 PU communication check time 
interval
9999 (without 
communication check)
9999 (without 
communication check)
REMARKS
•For futher details, refer to the Inverter instruction manual (applied).
POINT
Support GX Developer ver.8.0 or more
GX Developer Setting
REMARKS
•Refer to  the Inverter instruction manual (applied) for wiring.
•Refer to the GX Developer manuals for the specifications related to GX Developer and the
personal computer that uses GX Developer.
GX Developer Version xx Operating manual
GX Developer Version xx Operating manual (startup)
•The programming tool that can be used is GX Developer only. (The A6GPP, A7PHP, etc.
cannot be used.)
3-phase AC 
power supply
FR-A700
RS-232C/
RS-485
converter
GX Developer:
Programming tool
PU connector
Motor
PLC series
ACPU
PLC type
A0J2H
[Project data list]
→[Parameter]→[PLC parameter]→[A parameter]
→«Memory capacity» tab→"Program capacity"→"Sequence"→"main"
1k step