Листовка для Toshiba MBSB80-225-43

Скачать
Страница из 1
11.8"
42.4"
Left Side View
30.1"
Front View
TITLE
DRAWING NO.
REV.
NOTES
A
B
C
D
E
F
G
H
I
J
1
2
3
4
5
6
7
8
9
10
1
2
3
4
5
6
7
8
9
10
150kVA G8000 Series UPS
3-Breaker Maintenance Bypass Panel
MBSB80-225-43
1.0
52C
52M
52L
Maintenance
Bypass Breaker
225 Amp M.L.O.
w/ (1) #6-250kcmil 
Lug per Phase (typ)
Front View
(Door Removed)
27.0"
39.3
"
Utility Feed
UPS Bypass 
Input Breaker
UPS Output 
Breaker
225 Amp Box-
Mounted Neutral w/ 
(2) #6-250kcmil Lugs
0.5" Dia. 
Mounting Hole (4)
To Critical Load
A
B
C
N
Part No.
UPS 
KVA
Breaker
Type
Voltage
kAIC rating at 
480/600V
UPS Output 
Amp Rating
150
MBSB80-225-43
FD
480/600
25/14
180
Enclosure
Box/Trim
Finish
Breakers
Weight
- NEMA 1, Surface-Mount (UL Listed).
- 12-Gauge painted steel, trim held with adjustable clamps; Door equiped
   with one 3x5 directory cardholder and Corbin type 15767 Snaplock.
- Beige polyester powdercoat on all surfaces, treated with sealer.
- Cutler-Hammer thermal-magnetic type, 225A frame, 3-pole, trip settings as
  shown, supplied with (1) #4-4/0 terminal lug per phase.
- Approximately 190 lbs total.
Feed From Utility
Feed To Critical Load
52C
225AT
52M
225AT
52L
225AT
ST
A
B
C
A
B
C
A
B
C
A
B
C
Feed 
from 
UPS 
Output
Feed to 
UPS 
Input
N
1) This drawing is for illustration purposes only and is subject to change without notice. TIC
     is not responsible for any errors or omissions.
TOSHIBA
INTERNATIONAL CORPORATION
Houston Texas, USA
THIS  MATERIAL IS THE EXCLUSIVE PROPERTY OF 
TOSHIBA INTERNATIONAL CORPORATION AND SHALL NOT 
BE REPRODUCED, USED, OR DISCLOSED TO OTHERS 
UNLESS PRIOR WRITTEN AUTHORIZATION IS OBTAINED.
Drawn by 
EO
Date 07/07/04
Approved by 
JIS
Date 07/07/04