2.4. 
Status indicator 
The PDP002Z has two LEDs, ST (status) and DX (data exchange) to indicate the 
statuses of PROFIBUS-DP and the PDP002Z itself. 
 
ST (Status): Red LED
 
LED Meanings 
Off 
No diagnostics present 
Flashes 
Waiting for parameterisation or configuration 
Lights 
DP status error 
* For example, a station address is not setcorrectly. 
 
DX (Data exchange): Green LED.   
Indicates the status of the PROFIBUS network. 
It lights when the PDP002Z is on-line and data exchange is possible. 
 
2.5. 
Communications-related parameters
 
 
Parameter 
Function 
Adjustment range 
Default setting
f830
Communication 
option setting 1 
(PPO TYPE) 
0: None 
1: PPO TYPE 1 
2: PPO TYPE 2 
3: PPO TYPE 3 
4: PPO TYPE 4 
f831 
f846 
Communication option 
setting 2 - 13 
Refer to section 4. 
f851 
Inverter operation at 
the communications 
loss action 
(Network wire breaks) 
0: Stop and break of connection 
1: None 
2: Deceleration stop 
3: Coast stop 
4: Emergency stop 
5: Preset speed operation command 
(Operating at the preset speed operation 
frequency set with f852)   
f852 
Preset speed 
operation selection 
0: None 
1 to 15: Preset speed 
f853 
Monitoring of 
communication 
device station 
address 
Displays the station address assigned with the 
DIP switch. 
0 to 125 
f854
** 
Monitoring of 
communications 
device’s baud rate 
Displays the network communication speed set 
with the DIP switch. 
0: 12 
Mbit/s 
1: 6 
Mbit/s 
2: 3 
Mbit/s 
3: 1.5 
Mbit/s 
4: 500 
kbit/s 
5: 187.5 
kbit/s 
6: 93.75 
kbit/s 
7: 45.45 
kbit/s 
8: 19.2 
kbit/s 
9: 9.6 
kbit/s 
255: Disabled 
* When the parameters are changed, the power must be cycled to the VF-AS1/PS1 for 
the changes to take effect. 
** The baud rate of the PDP002Z is automatically set by configuration a baud rate for the 
master.
 
 