G8000 Series Installation and Operation Manual
CAUTION
Install the UPS in a controlled environment.
Improper storage and installation environment may deteriorate 
insulation, shorten component life and cause malfunctions.
See Table 5.1 - UPS Installation Environment Standards
DO NOT tilt the UPS more than 10° from upright position.
Tilting the UPS more than 10° may cause crushing, trapping or other 
personal injuries and cause physical damage to internal components.
WARNING
Keep the SPECIFIED CLEARANCE around the UPS.
Inadequate  space  around  the  UPS  makes  it  difficult  to  perform 
maintenance/inspections,  will  lead  to  insufficient  ventilation,  and/or 
cause malfunctions.
Install anchor bolts to secure the UPS to the installation floor.
The UPS may fall during an earthquake if the anchor bolts are not 
installed and secured.
Only factory authorized personnel should relocate, modify, or 
replace parts in the UPS after initial installation.
Electrical shock, injury or UPS failure may occur if non-authorized 
technicians attempt to modify or relocate the UPS.
Please contact Toshiba Customer Support Center if you plan to move 
or make modifications to the UPS
5    Installation Precautions