G8000 Series Installation and Operation Manual
FIGURE 11.14 - EARTH GROUND WIRE CONNECTIONS
G8000 - 80/100 kVA 
12 mm or 1/2 in. 
Terminal
10 mm or 
7/16 in. Bolt
Feed-through opening
AWG 2 
(38 mm
2
ground 
wire
To facility 
earth ground
Ground bus
G8000 - 300 kVA
Through conduit landing 
plate on top (recom-
mended)
Alternate ground 
wire location
Note:  Use either the top or 
the bottom grounding point, 
but not both. Doing so may 
degrade the performance of 
the unit.
10 mm or 
7/16 in. Bolt
Facility earth ground.  
Ground wire routing through 
top conduit landing plate.
Ground bus
G8000 - 150/225 kVA
Ground bus
12 mm or 1/2 in. 
Terminal
10 mm or 
7/16 in.  Bolt
Feed-through opening
AWG 2 (38 mm
2
ground wire
To facility 
earth ground
Facility earth ground.  
Alternate ground wire routing 
through top conduit landing 
plate.
Note:  Use either the top 
or the bottom access for 
the ground wire to connect 
to the ground buss, but 
use only one ground wire.
G8000 - 500 kVA
AWG 1/0 (50 mm
2
ground wire
12 mm or 1/2 in. 
Terminal
10 mm or 
7/16 in.  Bolt
Ground 
bus