Справочник Пользователя для Toshiba 4200FA CT/XT

Скачать
Страница из 68
TOSHIBA 
 
5.6 4200FA 50kVA w/Internal Transformer 
 
 Model 
Number 
T42#3*500#AMXN 
  
Input 
# =
(B: 208; H: 220; C: 240; N: 380–415; D: 480; M: 600) VAC 
  
Output 
*=
(F: 208; H: 220 wye; J: 240; P: 380–415 wye; K: 480 wye; M:600) 
 
Rated Output Capacity 
50 kVA 
 
External Dimensions 
W x D x H  (cm) 
35.5” X 38.3” X 59.3”  
(90.1 cm x 97.2 cm x 150.6 cm) 
Rated Voltage 
208 VAC 
Voltage Variation 
+10% to -30%; (-15% to -30%) **** 
Rated Frequency 
50 / 60 Hz 
Input Cables Required 
3 phase ; 3 Wire + GND 
Dual Input Option Cables required 
3 phase ; 4 Wire + GND  
* Power Factor 
Greater than 0.98 when in inverter mode 
Required Input kVA 
50 kVA 
Walk-in Function 
From 20% to 100% over 5 seconds 
Inrush Current 
Less than 8 times the rated current under synchronous operation 
Current Limit 
115% maximum 
Input 
* Harmonic Currents 
Less than 3% THD 
DC Nominal (Voltage Range) 
288 VDC (216 to 332 VDC) 
Float Charge (Regulation) 
324.0 VDC (
± 2%) 
Ripple Voltage 
0.5 V R.M.S. 
**Rated Back-up Time 
Refer to Battery System Manual 
Battery 
Rated Charge Current 
11.5 Amps 
Rated Voltage 
(Determined by Output Transformer internal to the unit) 
Rated Current 
VA / Nominal Output Voltage / 1.73 
Rated Power Factor 
0.8 lagging 
Output Cables Required 
3 phase ; 4 Wire + GND 
Voltage Regulation (phase-phase) 
± 2% (0–100% balanced load);  
± 3% (0–100% unbalanced load) 
Voltage Adjustment Range 
± 5V Manually from key pad 
Phase Displacement 
± 2° (0–100% balanced load);  
± 4° (unbalanced load) 
Rated Frequency 
50 / 60 Hz 
Frequency Regulation 
± 0.1% in free running mode 
Frequency Synchronous 
± 0.5/1.0/1.5 Hz (± 1.0 Hz. std.) 
switch selectable by qualified technician 
Frequency Slew Rate 
1 Hz/s to 3Hz/s(in 0.5 Hz steps) 
Voltage Transients 
(Recovery time: 50 ms) 
± 5% (100% load step change); 
± 3% (loss or return of input voltage); 
± 8% (transfer of bypass to inverter) 
Inverter Overload Capacity 
125% 90 sec; 150% 30 sec 
Bypass Overload Capacity 
1000% 10 ms; 125% 10 min. 
Crest Factor 
2.5–3.0 within the kW range 
Neutral Line Conductor 
1.73 (200%) times line rating 
Harmonic Voltage Distortion 
1.5% max (linear load) 
Output 
Inrush Current protection 
Automatic Transfer to bypass, then retransfer to inverter 
Efficiency (Typical) 
AC/DC/AC: 81%; DC/AC: 85% 
Heat loss to be removed 
30,874 BTU/hr   (7,778 kcal/hr) 
Audible Noise 
~65dB @ 1 meter from the front of the unit 
Operating Temperature 
32 – 104 
°F (0 – 40 °C); optimal temperature is 77 °F (25 °C) 
Operating Humidity  
30–90% RH (non condensing) 
Environment 
Altitude *** 
Less than 2000 meters 
Items marked with an (*) are specified at rated conditions under balanced linear loads. 
(**) Battery backup time may vary depending on the operating conditions and ambient temperature at the installation site, and an initial 
charge time of 24 hrs is necessary to obtain proper battery performance level before the unit is placed in operation. 
(***) At 6600-ft (2000 m) above sea level, output capacity should be derated by 3% (Consult Factory for higher elevations). 
(****) Prolonged operation at this level requires some derating of the output capacity. 
4200FA CT/XT User’s Manual 
 
 
36