6.7 Battery 
Recharging 
 
The illustration below shows a graphical representation of the UPS battery recharge  
 
process after a full discharge. 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
The recharge process usually consists of three steps. During the first step, the charging 
current is maintained at approximately 4.0 amperes for the 15/25/30 kVA with internal 
batteries, 10.0 amperes for the 15/25/30 kVA with internal transformer and approximately 
11.5 amperes for all 50 kVA models. This current is the maximum value that can be used 
to charge the batteries (for minimal recharge time) while assuring safety and long battery 
life. In the second step, constant-voltage control starts and current gradually decreases as 
the batteries charge to their normal fully charged state.  In the third step, a slight "trickle" 
current continues to flow into the batteries to keep them fully charged and "floating" at the 
normal DC Voltage level. A full recharge usually  requires approximately 24-72 hours (90% 
recharge in 10 X discharge time) after a  complete discharge.  
 
 
The following chart shows the rated maximum and minimum battery voltages, and the 
 
charge current for each of the sizes while the unit is maintained in a 75 °F (24 
°C) ambient. 
 
Rated Battery Voltages 
15/25/30 kVA  
50kVA 
Model 
Internal 
Battery 
Internal 
Transformer 
Internal 
Battery 
Internal 
Transformer 
V float 
324.0 VDC 
324 VDC 
324 VDC 
V min 
216 VDC 
216 VDC 
216 VDC 
I charge 
4.0 A 
10.0 A 
11.5 Amps 
 
4200FA CT/XT User’s Manual 
 
 