TOSHIBA
 4200FA XT UPS 
Installation Planning Guide for 15-80kVA UPS 
Standard System: 480v Input, 208/120V Output 
Rev. 1.02 
Page 1 of 2 
4200FA-IPG-480v-XT1 
 
 
General Mechanical Information 
Dimensions 
 (W  x D x H) 
Approximate Full-Load Heat Loss 
UPS kVA/ kW Rating 
Inches 
Weight  
Lbs. 
kBTU’s / Hr 
15 kVA/12 kW 
20 x 36.25 x 59.85 
1,260 
5.7 
25 kVA/ 20 kW 
20 x 36.25 x 59.85 
1,275 
7.6 
30 kVA/ 24 kW 
20 x 36.25 x 59.85 
1,275 
9.1 
50 kVA/ 40 kW 
35.59 x 38.19 x 59.39 
2,523 
17.7 
80 kVA / 64 kW 
44 x 31 x 74 
2,200 
40.0 
 
Primary AC Input (480V 3-Phase / 3-Wire) 
Maximum Input Power 
Demand 
Suggested External 
Overcurrent Protection 
Suggested Minimum Feeder 
Wire Size Per Phase 
Suggested Maximum Feeder Length 
For Min. Wire Size in Steel Conduit 
kVA 
PF 
Amps 
Amps 
AWG or kcmil at 75º C Temp. Rating 
Feet 
15 
>0.97 
20 
25 AT 
(1) x 10 
480 
25 
>0.97 
33.4 
40 AT 
(1) x 8 
480
 
30 
>0.97 
40 
45 AT 
(1) x 8 
480
 
50 
>0.97 
66.8 
75 AT 
(1) x 4  
480
 
80 
>0.98 
105.9 
125 AT 
(1) x 1  
480 
 
Optional Alternate AC Input (208/120V 3-Phase / 4-Wire) 
Maximum Input Power 
Demand 
Suggested External 
Overcurrent Protection 
Suggested Minimum Feeder 
Wire Size Per Phase / Neutral 
Suggested Maximum Feeder Length 
For Min. Wire Size in Steel Conduit 
kVA 
Amps 
Amps 
AWG at 75º C Temp. Rating 
Feet 
15 
41.6 
60 AT 
(1) x 8 / (1) x 6 
480 
25 
69.4 
90 AT 
(1) x 4 / (1) x 2 
480
 
30 
83.3 
110 AT 
(1) x 3 / (1) x 1 
480
 
50 
138.8 
175 AT 
(1) x 1/0 / (1) x 4/0 
480
 
80 
222.1 
300 AT 
(1) x 4/0 / (1) x 400  
480 
 
Battery Input (288VDC Nominal) 
Battery Capacity Required 
for Full Load Output 
Maximum Discharge 
at Full Load Output 
Suggested External 
Overcurrent Protection
Suggested Minimum Feeder 
Wire Size Per Phase 
Suggested Maximum Feeder Length 
For Min. Wire Size in Steel Conduit 
 
kWB 
Amps DC 
Amps 
AWG or kcmil at 75º C Temp. Rating 
Feet 
15 
13.33 
61.7 
90 AT 
(1) x 6 
70 
25 
22.22 
102.8 
125 AT 
(1) x 2 
70 
30 
26.67 
123.0 
175 AT 
(1) x 1  
70 
50 
44.44 
205.7 
225 AT 
(1) x 4/0  
70 
80 
71.11 
329.2 
400 AT 
(2) x 3/0  
70 
 
AC Output (208/120V 3-Phase / 4-Wire) 
Rated Output Power 
Suggested External 
Overcurrent Protection 
Suggested Minimum Feeder 
Wire Size Per Phase / Neutral 
Suggested Maximum Feeder Length 
For Min. Wire Size in Steel Conduit 
kVA 
PF 
Amps 
Amps 
AWG or kcmil at 75º C Temp. Rating 
Feet 
15 
0.8 
41.6 
60 AT 
(1) x 8 / (1) x 6 
380 
25 
0.8 
69.4 
90 AT 
(1) x 4 / (1) x 2 
380 
30 
0.8 
83.3 
110 AT 
(1) x 3 / (1) x 1 
380 
50 
0.8 
138.8 
175 AT 
(1) x 1/0 / (1) x 4/0 
380 
80 
0.8 
222.1 
300 AT 
(1) x 4/0 / (1) x 400  
380