Chapter 8: Troubleshooting
233
 
Power Supplies
VTraks are equipped with redundant power supplies. The 
advantage of dual power supplies is that, should one fail, the 
other will continue powering the subsystem until the faulty one 
can be replaced. VTrak is capable of operating on a single power 
supply. As a result, if one power supply fails you must watch the 
front panel LEDs or WebPAM PROe in order to become aware of 
the condition.
The power supplies are hot-swappable, meaning you can leave 
the VTrak running when you replace the bad one. Be careful, 
however, to remove the faulty power supply and not the good 
one, or VTrak will come to an immediate stop and your data will 
be unavailable until the system is powered and booted again. 
As noted above, if a power supply fan fails, you must replace the 
power supply. Without the fan to cool it, the power supply will 
overheat and eventually fail anyway. 
No tools are required for the procedure. See your page 171 for 
instructions on replacing a power supply.
Battery
VTrak uses a battery as backup power for the cache. Should a 
power failure occur, the battery enables the cache to hold data up 
to 72 hours. The battery recharges during normal VTrak 
operation. 
In most cases, installing a replacement battery will correct a 
marginal or failed condition. The battery is located on the left 
cooling unit. Remove the cooling unit for access. The battery is 
hot-swappable.
No tools are required for the procedure. See See page 175 fo
instructions on replacing the battery.