Chapter 2 - SmartController Installation
30
Adept SmartController User’s Guide, Rev. E
NOTE: If you are replacing an existing CF, the original must be sent to 
Adept for replacement. Press the button inside the CF compartment to 
eject the original card, remove it, and return it to Adept. Contact Adept 
Customer Service for assistance.
3. Carefully remove the CF from the READ ME FIRST box or shipping container. 
Locate the CF slot and position the card so its connector is facing towards the 
SmartController and the label is facing up. 
4. Insert the CF into the SmartController.
NOTE: Your licenses were installed onto the CF at the factory when it was 
initialized. Your licenses must be reinstalled onto a new CF by using the 
provided passwords and the V
+
 INSTALL monitor command. These 
passwords are provided in a box or folder labeled READ ME FIRST.
Once installed, Adept recommends that you do not repeatedly remove and insert the CF.
Connecting Power
The SmartController and sDIO require filtered 24VDC power. 
NOTE: Users must provide their own power supply. Make sure the power 
cables and power supply conform to the specifications below.
24VDC Power Specifications
NOTE: The power requirements for the user-supplied power supply will 
vary depending on the configuration of the SmartController and 
connected devices. A minimum configuration of the controller, front 
panel and MCP will require 1A at 24VDC. However, a 24V, 5A power 
supply is recommended to allow for additional current draw from 
connected devices, such as external IEEE 1394 devices and digital I/O 
loads.
Table 2-2. Specifications for 24VDC User-Supplied Power Supply
Customer-Supplied Power 
Supply
24VDC, 120W (5A).
Circuit Protection
Not more than 8A (below the 
amperage rating of the cable used).
Power Cabling
1.5 - 1.85 mm2 (16-14 AWG), 
maximum length 10 meters
Shield Termination
Braided shield connected to “-” 
terminal at the appropriate XDC 
connector.