  Type Test Specifications 
 
Electrical Safety 
Levels 
Comments 
Dielectric Withstand 
2 kV rms for 1 minute 
ANSI/IEEE C37.90 (1989) 
IEC 60255-5 (Section 6) 
High Voltage Impulse 
5 kV peak 
IEC 60255-5 (Section 8) 
Insulation Resistance 
500 VDC for 1 minute 
IEC 60255-5 (Section 6 
 
Electrical Environment 
Levels 
Comments 
High Frequency Disturbance 
(Oscillatory) 
2.5 kV @ 1MHz for 2s 
ANSI/IEEE C37.90.1 
IEC 60255-22-1 
IEC Surge 
4 kV / 2 kV 
IEC 61000-4-5 
(Level 4) 
IEC Fast Transient  
2 kV / 1 kV 
IEC 61000-4-4 
(Level 4) 
ANSI/IEEE Fast Transient 
4 kV 
ANSI/IEEE C37.90.1 
IEC Radiated RFI Immunity 
10 V/m 
IEC 61000-4-3 
ANSI/IEEE Radiated RFI 
Immunity 
35 V/m 
ANSI/IEEE C37.90.2 
ESD  
(Electrostatic Discharge) 
15 kV (air discharge) 
8 kV (contact) 
IEC 61000-4-2 
(Level 4) 
 
Atmospheric Environment 
Levels 
Comments 
Temperature (Dry Cold) 
-40°C 
IEC 60068-2-1 
Test Ad: 16 hrs @ -40°C 
Temperature (Dry Heat) 
85°C 
IEC 60068-2-2  
Test Bd: 16 hrs @ 85°C 
Humidity 
95% 
Non-condensing 
IEC 60068-2-30 
Test Db: 6 cycles, 55°C, 95% 
Humidity