31
For rack installations, the selected rack is grounded 
in accordance with the rack manufacturer’s 
recommendations. 
To reduce the possibility of personal injury or 
serious damage to the chassis, use at least two 
people 
to install the chassis. This is especially 
important for rack installations, because you must 
hold the chassis in place while you secure the 
chassis to the rack.
Bolt the rack to the floor.
Make certain that the rack is properly aligned and 
squared. Use a framing tool to ensure that the rack 
is squared.
Brace the top of the rack against the wall.
Provide sufficient space in front of and behind the 
chassis so that you can service it easily and provide 
proper ventilation.
Provide at least 7 cm (2.76 in.) on each side of 
the Switch 4007 chassis to ensure proper 
cooling in the chassis.
Provide at least 91.4 cm (36 in.) in back of the 
switch to remove and replace power supplies in 
the Switch 4007 chassis. 
Use the following guidelines to tighten screws to 
Torque Specification:
Faceplate thumbscrews — 3-5 in/lb 
(inch-pounds)
#10 screws for holding the chassis onto the 
rail — 22-25 in/lb
Power supplies to the chassis — 5-7 in/lb 
To ensure that you tighten screws to Torque 
Specification, use a torque screwdriver.
The following list shows the amount of rack space 
that is needed to install a Switch 4007 chassis in a 
Telco rack or a Metric rack.
Height — 30.98 cm / 12.2 in. 
The height of the chassis, allowing for some 
extension beyond the location of the upper and 
lower unit dividing lines.
Telco Rack Unit — 7 RU
The unit of measure is 1 Rack Unit (1.75 in. or 
4.45 cm). 
Metric Rack Unit — 12.5 SU
The unit of measure is 1 System Unit 
(25 millimeters).
Front clearance — 8 cm / 3 in.
This is the recommended minimum space required 
between the front of the chassis and another 
vertical surface (such as a rack door).
Rack-Mount Installation Recommendations
Use at least two people to install any chassis.
Before you install a chassis into a rack, make certain 
that the rack you are using is properly aligned and 
squared. Use a framing square to ensure that the rack 
is squared. Doing so makes installing the chassis into 
the rack easier.