F0020  Mains Phase Missing 
OFF2 
Possible Causes 
Fault occurs if one of the three input phases are missed while the pulses are enabled and drive is 
loaded 
Diagnose & Remedy  
Check the input wiring of the mains phases 
F0021 Earth 
fault 
OFF2 
Possible Causes 
Fault occurs if the sum of the phase currents is higher than 5 % of the nominal inverter current 
NOTE 
This fault only occurs on inverters that have 3 current sensors (Frame sizes D to F & FX, GX) 
F0022  Powerstack fault  
OFF2 
Possible Causes 
That hardware fault (r0947 = 22 and r0949 = 1) caused by the following events: 
(1)  DC-link overcurrent = short circuit of IGBT 
(2)  Short circuit of chopper 
(3) Earth fault 
(4)  I/O board is not properly inserted 
 
Frame sizes A to C (1),(2),(3),(4) 
 
Frame sizes D to E (1),(2),(4) 
 
Frame size F (2),(4) 
Since all these faults are assigned to one signal on the power stack, it is not possible to establish which 
one actually occurred. 
MM440 Frame size FX & GX: 
 
UCE failure was detected, when r0947 = 22 and fault value r0949 = 12 or 13 or 14, depending on 
UCE.  
 
I2C bus read out error, when r0947 = 22 and fault value r0949 = 21 (The power has to be switched 
OFF/ON). 
Diagnose & Remedy  
Check the I/O board. It has to be fully pressed home. 
F0023 Output 
fault 
OFF2 
Possible Causes 
One motor phase is disconnected 
F0030  Fan has failed 
OFF2 
Possible Causes 
Fan no longer working 
Diagnose & Remedy  
 
Fault cannot be masked while options module (AOP or BOP) is connected 
 
Need a new fan 
F0035  Auto restart after n 
OFF2 
Possible Causes 
Auto restart attempts exceed value of P1211 
F0041  Motor Data Identification Failure 
OFF2 
Possible Causes 
Motor data identification failed. 
Fault value =  0:  Load missing 
 
 
1:  Current limit level reached during identification. 
 
 
2:  Identified stator resistance less than 0.1 % or greater than 100 %. 
 
 
3:  Identified rotor resistance less than 0.1 % or greater than 100 %. 
 
 
4:  Identified stator reactance less than 50 % and greater than 500 %