LOGO! functions 
 
4.4 Special functions list - SF 
LOGO! 
Manual, 04/2011, A5E03556174-01 
177
 
4.4.8 
Random generator 
Short description 
The output of the random generator is set or reset within a configured time.     
 
Symbol in LOGO! 
Wiring 
Description 
Input En 
A positive edge ( 0 to 1 transition) at input En 
(Enable) triggers the on-delay time of the random 
generator. 
A negative edge ( 1 to 0 transition) at input En 
(Enable) triggers the off-delay time of the random 
generator. 
Parameter 
The on-delay is set at random to a value between 0 s 
and T
H
The off-delay is set at random to a value between 0 s 
and T
L
4
(Q
3DU
 
Output Q 
Output Q is set when the on-delay has expired and if 
En is still set. It is reset when the off-delay has 
expired, provided En was not set again meanwhile. 
Parameter T
H
 and T
L
 
Note the defaults of the T
H
 and T
L
 parameters listed in topic Time response (Pag151). 
The on-delay time TH and the off-delay time TL can be provided by the actual value of 
another already-programmed function. You can use the actual values of the following 
functions:  
●  Analog comparator (Page 218) (actual value Ax – Ay) 
●  Analog threshold trigger  (Page 213) (actual value Ax) 
●  Analog amplifier (Page 226) (actual value Ax) 
●  Analog multiplexer (Pag248) (actual value AQ) 
●  Analog ramp (Page 251) (actual value AQ) 
●  Mathematic instruction (Page 265) (actual value AQ) 
●  PI controller (Page 256) (actual value AQ) 
●  Up/down counter (Pag201) (actual value Cnt) 
 
If your LOGO! is a LOGO! 0BA7, you can additionally use the actual values of the following 
functions: 
●  Analog filter (0BA7 only) (Page 271) (actual value AQ) 
●  Average value (0BA7 only) (Page 276) (actual value AQ) 
●  Max/Min (0BA7 only) (Pag273) (actual value AQ) 
●  On-delay (Page 160) (current time Ta)