Справочник Пользователя для Liebert POWER PROTECTION STATIC TRANSFER SWITCH

Скачать
Страница из 152
Communication Interfaces
80
Group 3: 
User 
Settings
1
SRC1 Fast Undervoltage 
Setpoint    
Integer
In % of nominal below nominal
2
SRC1 Slow Undervoltage 
Setpoint    
Integer
In % of nominal below nominal
3
SRC1 Slow Undervoltage 
Detect Delay
Integer
In number of lines cycles
4
SRC1 Overvoltage 
Setpoint          
Integer
In % of nominal above nominal
5
SRC1 Overvoltage Detect 
Delay      
Integer
In 1/4 lines cycles
6
SRC1 I peak Transfer 
Setpoint      
Integer
x 10
7
SRC2 Fast Undervoltage 
Setpoint    
Integer
In % of nominal below nominal
8
SRC2 Slow Undervoltage 
Setpoint    
Integer
In % of nominal below nominal
9
SRC2 Slow Undervoltage 
Detect Delay
Integer
In number of lines cycles
10
SRC2 Overvoltage 
Setpoint          
Integer
In % of nominal above nominal
11
SRC2 Overvoltage Detect 
Delay      
Integer
In 1/4 lines cycles
12
SRC2 I peak Transfer 
Setpoint      
Integer
x 10
13
Max. Transfer Phase 
Angle              
Integer
In degrees
14
Output Frequency 
Deviation         
Integer
Freq. in Hz x 10
15
ReTransfer Delay Time              
Integer
In seconds
16
Horn Volume                        
Integer
Range: 1-10
17
Critical Option Enabling           
Bitpacked
18
Non-Critical Option 
Enabling       
Bitpacked
Group 4: 
Event Mask 
Settings
1 to 
63
Event Mask settings for 
faults
Event Mask
64 to 
143
Event Mask settings for 
alarms
Event Mask
Table 12
Group settings and values (continued)
Group
Item:
Description
Value Type
Value Notes