Automation and Drives - SCE 
 
 
 
 
T I A  Training Document 
Page 57 of 64 
  Module 
5.4 Exercise Example 
 
To accommodate the system step response, a few modifications have to be made in OB 35 and 
DB41. The following steps have to be performed for this: 
Save your old project under a new name, and change the wiring of (S)FB 41 as follows: 
1. With STEP7, specify the manipulated value directly.  
The manipulated value is to be specified in the network below in a way that with a switch  
S1 (I 124.0), a selection can be made between two manipulated values. 
 
 
0.000000e+000  
//Manipulated value 0% as 32 bit floating point number 
 
 
UN 
I 124.0   
 
//Negation of S1 (I 124.0) 
 
 
SPB 
M001   
 
//Jump if RLO = 1 to label M001 
 
 
1.000000e+002  
//Manip.value 100% as 32 bit floating pt. nbr. 
 
M001: 
MD 20   
 
//Transfer the value to flag double word MD 20  
Now, for the switch position S1(I 124.0) ON, the manipulated variable y = 100%, and for OFF, the 
manipulated variable y = 0%. Consequently, a step of the manipulated value from 0 to 100% can be 
brought about with Switch S1.  (For systems that tend to overshoot, the high manipulated value 
should amount to 90% or less.). 
The external analog values and the manipulated value are assigned in OB1 as follows:   
 
MAN 
 
:= 
MD 20   
//Specify the manipulated value as manual value 
 
PV_PER 
:= 
PEW 130 
//Actual value x 
 
LMN_PER 
:= 
PAW 128 
//Manipulated variable  y 
 
 
 
 
 
 
 
 Switch manipulated value to manual 
mode
 
 
 
 
 
 
 
 
Preface    Fundamentals     Discontinuous Action Controller     Controller Block (S)FB41     Setting the System     Appendix 
B3 
Issued: 02/2008                                                                                                                                     Control Engineering with STEP 7