IEC 60870 Functions of the FP Web-Server 
 
FP Web-Server V2.11 
152 
13.1  IEC 60870 General Functions 
The following connections to the FP Web-Server are possible: 
1.  The PLC is connected to the FP Web-Server via a 3-pin RS232C up to 115200 bps (see 
PLC connection to the FP Web-Server (see page 162)). 
2.  IEC 60870-5-101 Unbalanced Communication (9-pin RS232C of the FP Web-Server 
unit) 
- directly via RS232C to the central station 
- Multipoint via C-Net (RS485) adapter (AFP8536) up to 19200 bps 
- Multipoint via FP Modem-EU (V.23 via twisted pair cable) with 1200 bps 
- PSTN modem dialup connection (extension specified by OHP). This connection 
receives calls from and/or dials out to the central station. Analog modem, ISDN 
adapter or GSM module can be used. 
3.  IEC 60870-5-104 communication (via RJ45 Ethernet connector of the FP Web-Server 
unit) 
- via Ethernet 
- TCP/IP communication also possible via PPP-Server and dialup modem 
connections 
Comment: 
If an IEC 60870-5-104 Ethernet connection is established from the central station to the FP 
Web-Server, an IEC 60870-5-101 connection via RS232C is impossible. As soon as there is no 
Ethernet connection, the IEC 60870-5-101 connection can be established via RS232C again. 
 
•  Using IEC 60870 communication the PLC needs to execute special IEC 60870 
function blocks. These PLC function blocks are delivered as an FPWIN Pro 
library together with the FP WEB Configurator Tool. The IEC 60870 FPWIN 
Pro library, accompanying examples and interoperability documentation can 
be installed from the FP WEB Configurator Tool CD-ROM. For details refer to 
the Library's online help (see page 156). 
•  If the IEC 60870 functions are to be used (checkbox "Enable IEC60870" is 
active), disable standard FP Web-Server's functions like http, email, PPP 
server or port function (see page 104
). If these standard functions are 
enabled at the same time as the IEC 60870 protocol, the reaction time and 
performance of the FP Web functions may slow down. 
•  If the 9-pin RS232C port is set up for IEC60870-5-101 communication, 
MEWTOCOL communication can take place. The IEC60870 polling from the 
central station must be stopped before MEWTOCOL communication can  be 
used. MEWTOCOL commands are sent directly to the PLC. This version only 
allows short (standard) MEWTOCOL commands.