CONFIGURE THE COMMUNICATIONS TAB
1. Connection Type: Specify the type of connection between the device driver and the relay unit.
•
DIRECT SERIAL: The relay unit is connected using an RS-232 to RS-422 converter or using an RS-422 PC serial port.
•
INTERNET PROTOCOL: The relay unit is connected to the serial port on a networked device.
•
MODEM: This feature is reserved for future development.
2. Settings: Complete the instructions provided below for the appropriate connection type specified in Step 1. The settings must match the
settings specified within the relay unit. Refer to the CM9760-REL installation/operation manual for information on unit settings.
Direct Serial Settings
Figure 118. Communications Tab for CM9760-REL Serial Settings
a.
Select the COM port the relay unit is connected to from the drop-down box.
b.
Set the baud rate to match the DIP switch settings on the relay unit’s IN port. 19200 is recommended. If the relay unit is daisy-chained
from another relay unit, use the same baud rate for all the units in the chain.
from another relay unit, use the same baud rate for all the units in the chain.
c.
The remaining settings should specify no parity, 8 data bits, 1 stop bit, and no flow control.
d.
Refer to Step 3 for instructions on completing the fields in the Miscellaneous section.
Internet Protocol Settings
Figure 119. Communications Tab for CM9760-REL IP Settings