Листовка для Liebert LM250120YARCE

Скачать
Страница из 1
 
Liebert Corporation • 1050 Dearborn Drive • PO Box 29186 • Columbus, OH  43229  
Phone 607-724-2484 • Fax 607-722-8713 • US & Canada 800-288-6169 
EMAIL: info@control-concepts.com • Web Site: www.Liebert.com    
82241 Rev 1
 
 
Example Part Number:    
LM250120YARCE
 
500kA per Phase (250kA per Mode), 
120/208V 3-Phase Wye, All Mode, 
Rotary Disconnect, LED’s, Alarm, 
 
Counter, & Dual Form C Contacts,  
NEMA 12 Enclosure
 
Liebert LM Series TVSS
 
Technical Specification
  
Maximum Continuous  
Operating Voltage (MCOV) 
...................... 120V 125%, all others 115% 
Fault Current Rating (AIC)....................... 200 kAIC 
Operating Frequency Range ................... 47 – 63 Hz 
Response Time ........................................ <0.5 ns 
Operating Humidity.................................. 0% to 95% 
Status Indication ...................................... LEDs, Audible Alarm, Dry Contacts  
Certifications ............................................ UL 1449 & 1283, CUL, NEMA LS1, 
                                                                     ISO 9001:2000 
Enclosure  ................................................ NEMA 12 
Warranty ................................................... 5 Years Parts 
 
 
UL 1449 second edition clamping data 
Configuration 
L-N 
L-G 
L-L 
N-G 
120S, 120Y 
400 
400 
700 
400 
240D 
700 
700 
346Y 
1200 
1200 
2000 
1200
 
230Y, 277Y 
700 
700 
1500 
700 
480D 
1500 
1500 
600D 
1800 
2000 
 
Job Name ____________________________
Model# ______________________________
Date ________________________________
Qty _________________________________
Quote# ______________________________
Source Configuration 
1 Phase, L-N, 2W+G 
N
 
1 Phase, L-L, 2W+G 
L
 
Split Phase, 3W+G 
S
 
3 Phase, WYE, 4W+G 
Y
 
3 Phase, WYE, 3W+G   
(No Neutral) 
X
 
3 Phase, Delta, 3W+G 
D
 
3 Phase, Delta Hi-leg, 4W+G 
H
 
 
Surge Rating 
60kA / 
mode 
060 
80kA / 
mode 
080 
100kA / 
mode 
100 
125kA / 
mode 
125 
150kA / 
mode 
150 
200kA / 
mode 
200 
225kA / 
mode 
225 
250kA / 
mode 
250 
 
Model # LM
    __ __ __    __ __ __   __   __   __   __   __ 
Modes of Protection 
All 
 
L-G Voltage
 
120V
 
120
 
208V  
208 
220V  
230 
230V  
230 
240V  
240 
277V  
277 
480V  
480 
600V 
600 
 
Connection Options 
Wire Lug 
Disconnect 
 
Enclosure 
NEMA 12 
(Standard) 
NEMA 3R 
NEMA 4 
NEMA 4X 
 
Monitoring Options 
Standard Monitoring System, 
LEDs, Audible Alarm,  
Dual Form C Contacts 
LEDs, Audible Alarm,  
Surge Counter,  
Dual Form C Contacts 
 
Dimensional data in inches and shipping weight in pounds 
Unit 
Options 
Wt. 
LM060 
LM080 
All 
16 
14 
16.75 
12 
0.31 
1.35 
32 
LM100 
LM125 
LM150 
All 
16 
14 
16.75 
12 
0.31 
1.84 
41 
LM200 
LM225 
LM250 
All 
20 
16 
21.25 
10 
0.44 
1.84 
56 
Life Cycle Surge Testing 
10kA, 20kV, IEEE Cat. C3 
Unit 
Per Mode 
Per Phase 
060-080 
8,000 
16,000 
100-150 
16,000 
32,000 
200-250 
24,000 
48,000 
EMI/RFI Noise Rejection 
Single 
Unit 
Frequency 
System 
Installation 
34dB 
100kHz 
51dB 
51dB 
1MHz 
94dB 
54dB 
10MHz 
114dB 
48dB
 
100MHz
 
120dB
 
E
 
D
 
C
 
B
 
G
A
 
F