Справочник Пользователя для Mitsubishi Electronics MELSEC-F

Скачать
Страница из 504
B-23
5 Buffer Memory (BFM)
5.3 Buffer Memory List (BFM)
A
Comm
on I
te
ms
B
FX
3U
-4AD
FX
3UC
-4
A
D
C
FX
3U
-4A
D
-A
D
P
D
FX
3G
-2A
D
-BD
E
FX
3U
-4DA
F
FX
3U
-4D
A
-AD
P
G
FX
3G
-1D
A
-BD
H
FX
3U
-3
A-
ADP
I
FX
3U
-4
A
D
-P
T
       
         
   -
A
D
P
J
FX
3U
-4A
D
-P
TW
     
        
      -
A
D
P
FX
3G
/FX
3U
/FX
3UC
 PLC User's Manual - Analog Control Edition
FX
3U
-4AD/FX
3UC
-4AD (4-channel Analog Input)
5.3
Buffer Memory List (BFM)
4AD incorporates the following buffer memories.
→ For a detailed description of the buffer memory, refer to Section 5.4 and subsequent sections.
*1.
If power failure occurs, the EEPROM will retain its data.
*2.
To specify the input mode of each channel, set each digit using hexadecimal numbers 0 to 8 and F.
*3.
Use b0 to b3.
BFM number
Description
Setting range
Initial value
Data type Reference
#0
*1
Input mode setting for channels 1 to 4
*2
H0000 at delivery
Hexadeci-
mal
Subsection 
5.4.1
#1
Not used
-
-
-
-
#2
Averaging time units for channel 1
1 to 4095
K1
Decimal
Subsection 
5.4.2
#3
Averaging time units for channel 2
1 to 4095
K1
Decimal
#4
Averaging time units for channel 3
1 to 4095
K1
Decimal
#5
Averaging time units for channel 4
1 to 4095
K1
Decimal
#6
Channel-1 digital filter setting
0 to 1600
K0
Decimal
Subsection 
5.4.3
#7
Channel-2 digital filter setting
0 to 1600
K0
Decimal
#8
Channel-3 digital filter setting
0 to 1600
K0
Decimal
#9
Channel-4 digital filter setting
0 to 1600
K0
Decimal
#10
Channel-1 data (current data or average data)
-
-
Decimal
Subsection 
5.4.4
#11
Channel-2 data (current data or average data)
-
-
Decimal
#12
Channel-3 data (current data or average data)
-
-
Decimal
#13
Channel-4 data (current data or average data)
-
-
Decimal
#14 to #18
Not used
-
-
-
-
#19
*1
Data change disable
Disables adjustment of the following buffer 
memory locations:
• Input mode specification (BFM #0)
• Initialization function (BFM #20)
• Input characteristics writing (BFM #21)
• Convenient functions (BFM #22)
• Offset data (BFM #41 to #44)
• Gain data (BFM #51 to #54)
• Automatic transfer-to data register 
specification (BFM #125 to #129)
• Data history sampling time setting (BFM #198)
To enable data 
change: K2080
To disable data 
change: Value 
other than K2080
K2080 at delivery
Decimal
Subsection 
5.4.5
#20
Initialization function:
Set "K1" in this buffer memory to perform 
initialization. At the completion of initialization, 
buffer memory will be automatically reset to 
"K0".
K0 or K1
K0
Decimal
Subsection 
5.4.6
#21
Input characteristics writing:
Write the input characteristics offset/gain value. 
At the completion of writing, buffer memory will 
be automatically reset to "H0000" (b0 to b3: 
OFF).
*3
H0000
Hexadeci-
mal
Subsection 
5.4.7