3 Wiring
3.3 Analog Output Line
FX
3G
/FX
3U
/FX
3UC
 PLC User's Manual - Analog Control Edition
FX
3G
-1DA-BD (1-channel analog Output)
3.3
Analog Output Line
*1.
Use 2-core shielded twisted pair cable for the analog output lines, and separate the analog output
lines from other power lines or inductive lines.
*2.
Ground the shielded wire at one point on the signal receiving side.
3.4
Grounding
Grounding should be performed as stated below.
• The grounding resistance should be 100
Ω or less.
• Independent grounding should be performed for best results.
When independent grounding is not performed, perform "shared grounding" as shown in the following 
figure.
→ For details, refer to User’s Manual - Hardware Edition of the PLC Series.
• The grounding wire size should be AWG22 to 20 (0.3 to 0.5 mm
2
).
• The grounding point should be close to the PLC, and all grounding wires should be as short as possible.
I+
VI-
V+
I+
VI-
V+
If voltage output is selected:
If current output is selected:
*1 Shield
Terminal
1DA-BD
1DA-BD
block
Terminal
block
*1 Shield
*2 Class-D
grounding
*2 Class-D
grounding
PLC
Other
equipment
PLC
Other
equipment
PLC
Other
equipment
Shared grounding
Good condition
Common grounding
Not allowed
Independent grounding
Best condition