LG SERIES GAS FRYERS 
VULCAN-HART                                                                                                                   F-32910 Rev. H (April 2008) 
-7-
 
 
 
Š 
Locate the fryer under a hood with adequate connection to an exhaust 
duct.  The hood must extend 6” (15 cm) beyond fryer on both sides. 
 
 
Š 
Clearance above the fryer should be adequate for combustion byproducts  
to be removed efficiently. 
 
Š 
An 18” (46 cm) minimum clearance should be maintained between the flue 
 vent and the filters of the hood venting system. 
 
Š 
Never make flue connections directly to the fryer. 
 
Š 
Do not obstruct the flow of the gases from the appliance.  Proper air  
balance should be maintained in the room. 
 
 
GAS CONNECTION 
 
 
  
         All gas supply connections and any pipe joint compound must be  
      
         resistant to the action of propane gases. 
 
The gas inlet is located on the lower rear of the fryer.  Codes require that a gas shutoff valve 
be installed in the gas line ahead of the fryer. 
 
The gas supply line must be at least the equivalent of ½” (12.7 mm) iron pipe for single units 
and 1-1/4” (31.75 mm) for batteries.  If using the optional quick-disconnect flex hose, ¾” (19 
mm) iron pipe for single units and 1-1/4” (31.75 cm) iron pipe for batteries.