Справочник Пользователя для Vulcan-Hart LG300

Скачать
Страница из 18
LG SERIES GAS FRYERS 
VULCAN-HART                                                                                                                   F-32910 Rev. H (April 2008) 
-8-
 
 
 
 
Make sure the pipes are clean and free of obstructions, dirt, and piping compound.  A 
battery requires one or two connections of appropriate size for the gas requirement. 
 
 
  
 Prior to lighting, check all joints in the gas supply line for leaks. 
                          Use soap and water solution.  Do not use an open flame.  
             
   
 
After piping has been checked for leaks, fully purge gas pipes to remove air. 
 
 
GAS PRESSURES (ALL MODELS):  
 
The gas pressure should be set at 4” W.C. (Water Column) (0.8 kPa) for natural gas and 10” 
W.C. (2.75 kPa) for propane gas. If incoming pressure exceeds ½ PSI (3.45 kPa), an 
additional pressure regulator must be installed.  
 
 
TESTING THE GAS SUPPLY PIPING SYSTEM:  
 
When test pressures exceed ½ PSI (3.45 kPa), the fryer and its individual shutoff valve must 
be disconnected from the gas supply piping system.   
 
 
 
 
When test pressures are ½ PSI (3.45 kPa) or less, the fryer must be isolated from the gas 
supply piping system by closing its individual shutoff valve. 
 
Fryers with Casters: 
 
Separate instructions for installing casters are included with the casters: 
 
Š 
The installation shall be made with a connector that complies with the 
Standard for Connectors for Movable Gas Appliances, ANSI Z21.69 or 
Connectors for Moveable Gas Appliances, CAN/CGA-6.16, and a quick-
disconnect device that complies with the Standard for Quick-Disconnect Devices 
for Use with Gas Fuel, ANSI z21.41 or Quick-Disconnect Devices for Use with 
Gas Fuel, CANI-6.9.