Справочник Пользователя для Mitsubishi Electronics SW1-GTD2-O-E

Скачать
Страница из 234
4 - 25 
4 - 25 
 
4.12 Data Check   
Whether the monitor screen data created with the GT Designer2 has an error or not is checked.   
 
  Open all screens for data check. Unopened screens are not data checked.   
 
 Select [Tools]    [Data Check] menu.   
 
  The data check dialog box is displayed.   
Set the check items for data check and click the    Check    button.   
 
 
 
(Setting of GOT-A900 series) 
(Setting of GOT-F900 series) 
 
Item 
Description 
Check Item 
Items for data check are checked. 
 
 
 Touch 
Area 
Whether overlap of touch switch functions occurs is checked. 
• Touch switches are overlapped. 
• Numerical input/ASCII input is overlapped with touch switches. 
 
 
 
Key Count 
Whether the number of touch switch functions exceeds 256 on one screen is checked. 
 
 
 
Memory Store 
Object 
Whether the number of objects (alarm list, trend graph and scatter graph) which set the 
memory storage is 17 or more for each object is checked. 
 
 
 
Window Screen 
Data 
Whether the data list or the alarm history is set on the window screen is checked. (The 
data list and the alarm history cannot be displayed on the window screen.) 
 
 
 Scroll 
Object 
Whether multiple objects with scroll display (data list, alarm history and alarm list) are set 
on one screen is checked. 
 
 
 Report 
Data 
When the report screen is created, whether the numerical print or the comment print is set 
on the header is checked. 
 
 
 
Number of 
object entries 
Whether the number of objects that can be registered on one screen exceeds the limit is 
checked. 
 
 
 
Nest level of set 
overlay screens 
Whether the nest level of set overlay screens is within 5 that can be set on one screen is 
checked. 
 
 
 
Key window 
screen data 
Whether there is any object that cannot be set on the window screen is checked. 
 
 
 
Data Area 
Whether any object is set outside the screen range is checked. 
 
 
Carry out Checking during 
save or transfer 
Data check is automatically performed when a project is saved or a monitor screen data is 
transferred to the GOT.