3 - 48
3.7.2 Checking power supply capacity and I/O points
3 OPERATING PROCEDURE OF MELSOFT NAVIGATOR
iQ Works
3.7.2
Checking power supply capacity and I/O points
Check power supply capacity and I/O points of created system configuration.
This functions is not supported by FXCPU.
1.
Select [Workspace] 
⇒ [Check] ⇒ 
[Power Supply Capacity and I/O Points 
of Q/L Module Configuration] in the 
menu bar.
2.
The message shown on the left is 
displayed.
Read the message and click the 
 
button to display the "Result of Power 
Supply Capacity and I/O Points Check" 
window.
3.
Check for errors in the check result.
When an error exists in the check result 
(items displayed in red), options of modules 
for re-selection are displayed by clicking 
"Total Output Current" or "Total I/O Points". 
A message is displayed by clicking "Total 
Voltage Drop".
Read the message and correct the module 
configurations.
● "Total Output Current"
Values displayed under "Total Output Current" may be different from the total output current of module with latest 
version.
For the total output current of module with latest version, check the latest manuals of each module.
Select