Справочник Пользователя для National Instruments 321645c-01

Скачать
Страница из 554
Chapter 2
Function Reference — DIG_In_Port
©
 National Instruments Corporation
2-175
NI-DAQ FRM for PC Compatibles
DIG_In_Port
Format
status = DIG_In_Port (deviceNumber, port, pattern)
Purpose
Returns digital input data from the specified digital I/O port.
Parameters
Input 
Output 
Parameter Discussion
port is the digital I/O port number.
Range:
0 or 1 for the AT-AO-6/10, DAQCard-500/700, PC-TIO-10, PC-OPDIO-16, 
516 devices, AO-2DC, Am9513-based MIO devices, and LPM devices.
0 for the E Series devices, except the AT-MIO-16DE-10.
0 through 2 for the DIO-24 and Lab and 1200 Series devices.
0 and 2 through 4 for the AT-MIO-16DE-10.
0 through 3 for the VXI-AO-48XDC.
0 through 4 for the DIO-32F, DIO 6533 (DIO-32HS), and AT-MIO-16D.
0 through 11 for the DIO-96.
0 through 15 for the VXI-DIO-128.
0 for the PCI-4451 and PCI-4452.
0 through 3 for the PCI-4551 and PCI-4552.
pattern returns the 8-bit digital data read from the specified port. NI-DAQ maps pattern to 
the digital input lines making up the port such that bit 0, the least significant bit, corresponds 
to digital input line 0. The high eight bits of pattern are always 0. If the port is less than eight 
bits wide, NI-DAQ also sets the bits in the low-order byte of pattern that do not correspond 
to lines in the port to 0. For example, because ports 0 and 1 on the Am9513-based boards are 
Name
Type
Description
deviceNumber
i16
assigned by configuration utility
port
i16
digital I/O port number
Name
Type
Description
pattern
i16