When the unit  is installed into a woodburning fireplace, 
the minimum distance the mantel can be placed above 
the fireplace is governed by local building codes appli-
cable to woodburning fireplaces. Consult local authori-
ties having jurisdiction for these clearances.
For applications requiring the use of a Zero Clearance 
Kit, the minimum height a mantel can be installed above 
the fireplace is 24" (610mm) from the top of the upper 
louvres. The maximum mantel depth is 8" (200mm). 
(Fig. 2)  
The underside of the mantel will become 
warm. Use only finishes which are heat 
resistant and do not discolor.
Mantels
FP1325
Insert mantel
height
4/1/03   djt
24" Min.
(610mm)
FP1325
Fig. 2  Minimum mantel height above fireplace.
Framing & Finishing
For Zero Clearance Kit applications, it is important to 
determine the finished facing material before beginning 
to frame. This will allow for the thickness of the finishing 
material between the frame and the fireplace trim.
Similarly, consideration must be given to the 1" inch 
depth of the air inlet channel sitting on the fireplace 
base. Finishing material for the hearth should be flush 
with the top of the air inlet channel.
If the fireplace is installed at floor level a noncombus-
tible hearth must extend a minimum 12" (305mm) in 
front of the fireplace.
If the fireplace is recessed into the wall and at least 12" 
(305mm) above floor level, no hearth is required.
The use of wallpaper adjacent to this fire-
place is not recommended as high tem-
peratures given off by this fireplace may 
adversely effect the binders in the adhe-
sive used to apply the wallpaper.
NOTE:  Insulating around the fireplace will result in 
overheating and possible malfunctioning of the circulat-
ing fan.
Zero Clearance Applications
An alternate air supply is recommended 
with this component.
For installation other than in existing wood-
burning fireplaces such as new construction or renova-
tion projects, a Zero Clearance Kit must be used. The 
kit enables these inserts to be installed in combustible 
environments. Whenever using a Zero Clearance Kit, 
consideration must be given to the dimensions of the 
Zero Clearance Kit and the requirements of the Air Kit.
NOTE:  If a Zero Clearance Kit is required for mod-
els LHEC20/LHER20/LHEC30/LHER30 Natural Vent 
Inserts, only the CFM Corporation zero clearance 
kit HEZC is approved to be used. When using the 
HEZC with insert models LHEC20 or LHER20, the 
Trim Closure Kit, LHE20TCK, must also be installed.
35"
(889mm)
37¹⁄₄" (946mm)
FP1251
Insert framing 
and finishing
1/03
27¹⁄₄" (692mm)
19¹⁄₈"
(486mm)
Air Inlet Channel
Drywall
Finish Wall
Decorative Trim Kit
FP1351
Fig. 3  LHE  insert framing dimensions.