InRow RC Installation
28
Form C alarm contacts and shutdown input
A relay internal to the user interface is typically controlled by a user-defined alarm (malfunctioning fans, 
for example). Before an alarm is detected, the voltage on the COM terminal is routed to the NC terminal. 
When the alarm is activated, the relay is energized, causing the voltage on the COM terminal to be 
routed to the NO terminal. The NO and NC terminals may be connected to remote indicator lights, a 
warning buzzer, or another device to alert an operator to the presence of an alarm condition.
A remote disconnect switch may be connected to the shutdown inputs.
Leak detector port
Rope water detector (AP9325). 
Up to four optional rope water 
detectors can be installed in series. The rope water detector 
connects to the RJ-45 leak detector port located at the top of the 
interface box.
See the “Rope Water Detector” installation sheet 
(supplied with the kit) for installation and setup information.
Remote switch using
internal power (24 Vdc
shown)
Field-supplied voltage
(12/24 Vdc or Vac)
n1
5
84