Wiring Recommendations
105
09/2003
©
 2000–2003 Schneider Electric All Rights Reserved
Ratings for Input Line Currents, Type N 208 to 230 Vac
Single-Phase Input with Three-Phase Output / Three-Phase Input with Three-Phase Output
 
Ratings for Input Line Currents, Types E and F 200 Vac -10% / 240 Vac +10%
Three-Phase Input with Three-Phase Output
Drive Controller 
Catalog Number 
Motor Power at 4 kHz 
Switching Frequency
Rated 
Output 
Current (In)
Input Line Current
5000 AIC
with Additional 3% 
Line Impedance
kW
HP
A
200 V
A
240 V
A
200 V
A
240 V
A
ATV58EU29M2ZU
1.5
2
7.8
9.7
8.3
6.6
5.9
ATV58EU41M2ZU
2.2
3
11
13.4
11.4
9.5
8.5
Ratings for Input Line Currents, Types E and F 400 Vac -15% / 460 Vac +20%
Three-Phase Input with Three-Phase Output
Drive Controller 
Catalog Number 
Motor Power at 4 kHz 
Switching Frequency
Rated 
Output 
Current 
(In)
Input Line Current
5000 AIC
with Additional 3% 
Line Impedance
400 V
kW
460 V
HP
A
400 V
A
460 V
A
400 V
A
460 V
A
ATV58EU18N4ZU
0.75
1
2.3
3.4
2.6
1.9
1.6
ATV58EU29N4ZU
1.5
2
4.1
6
4.5
3.3
3
ATV58EU41N4ZU
2.2
3
5.8
7.8
6
4.8
4.2
ATV58EU54N4ZU
3
7.8
10.2
7.8
6.3
5.6
ATV58EU72N4ZU
4
5
10.5
13
10.1
8.6
7.2
ATV58EU90N4ZU
5.5
7.5
13
17
13.2
11.8
10.1
208 to 230 Vac, Single-Phase Input with 3-Phase Output
Drive Controller Catalog Number
Dissipated Power at Rated 
Load (Total)
Short Circuit Rating
Input Line Current
 
W
A  RMS  sym.
A
A
ATV58NU09M2•
42
2,000
5.6
4.7
ATV58NU18M2•
64
2,000
9.8
8.3
ATV58NU29M2•
107
5,000
18.5
15.6
ATV58NU41M2•
160
5,000
25.6
21.6
When these drive controllers are used with a single-phase input, a line reactor (3% minimum) must be used.
208 to 230 Vac, 3-Phase Input with 3-Phase Output
Drive Controller Catalog Number
Dissipated Power at Rated 
Load (Total)
Short Circuit Rating
Input Line Current
 
W
A  RMS  sym.
A
A
ATV58NU29M2•
107
5,000
9.7
8.3
ATV58NU41M2•
160
5,000
13.4
11.4
ATV58NU54M2•
190
5,000
17.2
15
ATV58NU72M2•
240
5,000
22.4
19.5
NOTE: The input 
conductor ampacity 
rating should not be 
less than the 
ampacity rating 
selected based on the 
rated controller output 
current.