sensor temperature   defrost termination temperature 
or defrost duration (F1) ends, the heater and defrost 
will stop after the draining time (F6). The cold‐room 
temperature   (set temperature + hysteresis), the 
compressor will starts and go back to refrigeration 
status.  
When the defrost interval time (f2) is set”00”, the 
function of the automatics defrost will be cancelled. 
Temperature displayed when defrost: If F4 is set “01”, it 
displays the temperature when the defrost starts. After 
defrost, It will continue to display this temp for 20 min 
and the defrost LED will begin flashing. It will then come 
back to normal temperature.  
•  Controlling the evaporator fan after defrost: 
Controlling by time: When F7 is set “00” after 
defrost, the compressor works for F8 and then the 
fan restarts. After defrost and the first working 
mode, the fan will follow the mode of F5. 
Controlling by temperature: When F7 is set “01” 
after defrost, when the evaporator temperature 
reaches F9, the fan restarts. After defrost and the 
first working mode, the fan will follow the mode of 
F5. 
•  Sensor failure work mode: If the cold‐room sensor is 
short circuited or overheated, “HH” will be 
displayed. If the cold‐room sensor is in an open 
circuit or the temperature is too low then “LL” is 
displayed. At that time the compressor will 
automatically go to a cycle of 45 min on and 15 min 
off. When the evaporator sensor fails or surpasses 
the displayed range, the defrost termination will be 
just controlled by the defrost duration.