Lag Chiller Shutdown Requirements 
The following conditions must be met in order for the lag chiller to be stopped. 
1. Lead chiller COMPRESSOR MOTOR LOAD value is less than the lead chiller percent 
capacity plus 15%. 
Note: Lead chiller percent capacity = 100 – LAG PERCENT CAPACITY 
The LAG PERCENT CAPACITY value is configured on the Lead/Lag Configuration screen. 
2. The lead chiller chilled water temperature is less than the CONTROL POINT plus 1/2 of the 
WATER/BRINE DEADBAND. 
3. The configured LAG STOP TIMER entry has elapsed. The LAG STOP TIMER is started 
when the CHILLED WATER TEMPERATURE is less than the CHILLED WATER 
CONTROL POINT plus 1/2 of the WATER/BRINE DEADBAND and the lead chiller 
COMPRESSOR MOTOR LOAD is less than the lead chiller percent capacity plus 15%. The 
timer is ignored if the chilled water temperature reaches 3° F (1.67° C) below the 
CONTROL POINT and the lead chiller COMPRESSOR MOTOR LOAD value is less than 
the lead chiller percent capacity plus 15%.
Faulted Chiller Operation 
If the lead chiller shuts down on an alarm (*) condition, it stops communication to the lag and 
standby chillers. After 30 seconds, the lag chiller will now become the acting lead chiller and will 
start and stop the standby chiller, if necessary.