Check Insulation Resistance (Hermetic Motor) 
Test the machine compressor motor and its power lead insulation resistance with a 500-v 
insulation tester such as a megohmmeter. (Use a 5000-v tester for motors rated over 600 v.) 
Factory-mounted starters do not require a megohm test. 
1. Open the starter main disconnect switch and follow lockout/tagout rules.
2. With the tester connected to the motor leads, take 10-second and 60-second megohm 
readings as follows: 
6-Lead Motor — Tie all 6 leads together and test between the lead group and ground. Next 
tie leads in pairs, 1 and 4, 2 and 5, and 3 and 6. Test between each pair while grounding the 
third pair. 
3-Lead Motor — Tie terminals 1, 2, and 3 together and test between the group and ground.
3. Divide the 60-second resistance reading by the 10-second reading. The ratio, or 
polarization index, must be one or higher. Both the 10- and 60-second readings must be at 
least 50 megohms. 
CAUTION
CAUTION
!
If the motor starter is a solid-state starter, the motor leads must be disconnected 
from the starter before an insulation test is performed. The voltage generated 
from the tester can damage the starter solid-state components.