Input the Design Set Points 
Access the LID set point screen and view/modify the base demand limit set point, and 
either 
the LCW set point 
or the ECW set point. The PIC can control a set point to either the leaving or 
entering chilled water. This control method is set in the Equipment Configuration table, Config 
table.
Input the Local Occupied Schedule (OCCPC01S)
Access the schedule OCCPC01S screen on the LID and set up the occupied time schedule 
per the customer’s requirements. If no schedule is available, the default is factory set for 24 
hours occupied 7 days per week including holidays. 
For more information about how to set up a time schedule, see the 
 section. 
The CCN Occupied Schedule (OCCPC03S) should be configured if a CCN system is being 
installed or if a secondary time schedule is needed. 
The Ice Build Occupied Schedule (OCCPC02S) should be configured for Ice Build 
applications.