To Read Refrigerant Pressures
 during pumpout or leak testing:
1. The LID display on the machine control center is suitable for determining refrigerant-side 
pressures and low (soft) vacuum. For evacuation or dehydration measurement, use a 
quality vacuum indicator or manometer to ensure the desired range and accuracy. This can 
be placed on the Schrader connections on each vessel (
 and 
by removing 
the pressure transducer. 
2. To determine utility vessel pressure, a 30 in.-0-400 psi (-101-0-2760 kPa) gage is attached 
to the vessel. 
3. Refer to 
 for valve locations and numbers.
CAUTION
CAUTION
!
Transfer, addition, or removal of refrigerant in spring-isolated machines may 
place severe stress on external piping if springs have not been blocked in both 
up and down directions.