Control Test 
The Control Test feature can check all of the thermistor temperature sensors, including those 
on the Options modules, pressure transducers, pumps and their associated flow switches, the 
guide vane actuator, and other control outputs, such as hot gas bypass. The tests can help to 
determine whether a switch is defective, or a pump relay is not operating, among other useful 
troubleshooting tests. During pumpdown operations, the pumps are energized to prevent 
freeze-up and the vessel pressures and temperatures are displayed. The lockout feature will 
prevent start-up of the compressor when no refrigerant is present in the machine, or if the 
vessels are isolated. The lockout is then terminated by the operator by using the Terminate 
Lockout function after the pumpdown procedure is reversed and refrigerant is added.
Table 8, A - N — LID Primary and Secondary Messages and Custom Alarm/Alert 
Messages with Troubleshooting Guides