6.5.4  Menu item Quick Setup
Level
Designation
Selection / entry field
Explanation
1.1.1
Language
Select menu language
German  ↑...
German language
French  ↑…
French language
English  ↑...^
English language
1.1.2
Location
0000000000
Location↑…↑...↑...^
Enter the name of the location (max. 
10 characters)
1.1.3
Maes.Inst
Select type of flow measurement
Volume  ↑…
Volume measurement
Norm. Vol. ↑…
 1
Standard volume flow measurement
Mass  ↑...^
Mass flow measurement
1.1.4
Max. Flow
Set maximum flow rate
2
m
3
/h
Unit  ↑...^
Select unit for volume flow 
measurement
888888888
Upp.Limit
00600.0000 or other value
m
3
/h  ↑…↑...↑...^
Enter value for the maximum volume 
flow
Display Unit / 
Display %Max Flow ↑...^
Display flow rate in units /
in % of maximum flow rate
3
m
3
/h norm
Unit  ↑...^
Select unit for standard volume flow 
measurement
00600.0000 or other value
m
3
/h  norm ↑…↑...↑...^
Enter value for the maximum 
standard volume flow rate
Display Unit / 
Display %Max Flow ↑...^
Display flow rate in units /
in % of maximum flow rate
4
kg/h
Unit
Select unit for mass flow 
measurement
00600.0000 or other value
kg/h ↑…↑...↑...^
Enter value for the maximum mass 
flow rate
Display Unit / 
Display %Max Flow ↑...^
Display flow rate in units /
in % of maximum flow rate
1.1.5
Min. Flow
001111111
00300.0000
m
3
/h  ^
The minimum flow rate value is 
factory-set.
1.1.6
Timeconst.
00002.0000
s ↑…↑...↑...^
Enter the time constant for the 
measured value output in seconds 
(0 – 20 s)
0: disabled
1 only with gas
2 available if Maes.Inst = Volume (see menu item 1.1.3)
3 available if Maes.Inst = Norm. Vol. (see menu item 1.1.3)
4 available if Maes.Inst = Mass (see menu item 1.1.3)