RL-854 Radio Control Unit
Type I, Style A
Operation
 2001 Siemens Airfield Solutions, Incorporated
96A0027L
Page 23
All rights reserved
Issued 5/01
The RL-854PR contains three 2-pole power relays that are rated for 25 amps
(resistance) per pole.  The auxiliary terminal strip TB1 handles up to AWG
10 wire. Wire the RL-854PR as follows:
1.  Terminal 1 and Terminal 2 - closes when 7-pulse relay is powered.
 
2.  Terminal 3 and Terminal 4 - closes when 7-pulse relay is powered.
 
3.  Terminal 5 and Terminal 6 - closes when 5-pulse relay is powered.
 
4.  Terminal 7 and Terminal 8 - closes when 5-pulse relay is powered.
 
5.  Terminal 9 and Terminal 10 - closes when 3-pulse relay is powered.
 
6.  Terminal 11 and Terminal 12 - closes when 3-pulse relay is powered.
 
7.  Terminal 13 - line (120 Vac), black wire.
 
8.  Terminal 14 - neutral (120 Vac return), white wire.
9.  Terminal 15 – earth ground, green wire.
 
This section describes operations of the RL-854 Radio Control unit.
The RL-854 is shipped for individual relay operation.  Under individual
relay 
operation:
  3 pulses closes the 3-pulse relay
 
  5 pulses closes the 5-pulse relay and opens the 3-pulse relay
 
  7 pulses closes the 7-pulse relay and opens the 5-pulse relay
The relay operation can be changed for incremental relay operation, which
is as follows:
  3 pulses closes the 3-pulse relay
 
  5 pulses closes the 5-pulse and 3-pulse relays
 
  7 pulses closes the 7-pulse and 5-pulse relays
Installing RL-854PR Radio
Controller 
(contd.)
4.  Operation
Incremental Relay Option