Справочник Пользователя для Mitsubishi Electronics FR-A740-0.4k to 500k

Скачать
Страница из 523
335
Communication operation and setting
4
4.24.5 Mitsubishi inverter protocol (computer link communication)
(1) Communication specifications
⋅ The communication specifications are given below.
(2) Communication procedure
*1
If a data error is detected and a retry must be made, execute retry operation with the user program. The inverter trips if the number of consecutive
retries exceeds the parameter setting.
*2
On receipt of a data error occurrence, the inverter returns "reply data 3)" to the computer again. The inverter trips if the number of consecutive
data errors reaches or exceeds the parameter setting.
You can perform parameter setting, monitor, etc. from the PU connector or RS-485 terminals of the inverter using
the Mitsubishi inverter protocol (computer link communication).
Item
Description
Related 
Parameters
Communication protocol
Mitsubishi protocol (computer link) 
Pr. 551
Conforming standard
EIA-485 (RS-485)
Number of inverters connected
1:N (maximum 32 units), setting is 0 to 31 stations
Pr. 117
Pr. 331
Communication 
speed
PU connector
Selected among 4800/9600/19200/38400bps
Pr. 118
RS-485 terminal
Selected among 300/600/1200/2400/4800/9600/19200/38400bps
Pr. 332
Control protocol
Asynchronous system
Communication method
Half-duplex system
Communication 
specifications
Character system
ASCII (7 bits or 8 bits can be selected)
Pr. 119
Pr. 333
Start bit
1bit
Stop bit length
1 bit or 2 bits can be selected
Pr. 119
Pr. 333
Parity check
Check (with even or odd parity) or no check can be selected
Pr. 120
Pr. 334
Error check
Sum code check
Terminator
CR/LF (presence or absence can be selected)
Pr. 124
Pr. 341
Waiting time setting
Selectable between presence and absence
Pr. 123
Pr. 337
⋅ Data communication between the computer and
inverter is made in the following procedure.
1)Request data is sent from the computer to the
inverter. (The inverter will not send data unless
requested.)
2)After waiting for the waiting time
3)The inverter sends reply data to the computer in
response to the computer request.
4)After having waited for the time taken for inverter
processing
5)Answer from computer in response to reply data
3) is sent. (Even if 5) is not sent, subsequent
communication is made properly.)
When data is read
When data is written
1)
5)
4)
3)
2)
*1
*2
Computer
(Data flow)
Inverter
Computer
(Data flow)
Inverter
Time