Справочник Пользователя для Mitsubishi Electronics FR-D740-012

Скачать
Страница из 294
24
Control circuit specifications
2.3.3
Wiring of control circuit
(1) Standard control circuit terminal layout
(2) Wiring method
Wiring
 Use a bar terminal and a wire with a sheath stripped off for the control circuit wiring. For a single wire, strip off the sheath of
the wire and apply directly.
Insert the bar terminal or the single wire into a socket of the terminal.
1) Strip off the sheath about the size below. If the length of the sheath peeled is too long, a short circuit may occur among
neighboring wires. If the length is too short, wires might come off.
2) Crimp the bar terminal.
 Insert wires to a bar terminal, and check that the wires come out for about 0 to 0.5 mm from a sleeve.
Check the condition of the bar terminal after crimping. Do not use a bar terminal of which the crimping is inappropriate, or
the face is damaged.
Introduced products on bar terminals :(as of Mar., 2008)
Bar terminal crimping tool: CRIMPFOX ZA3 (Phoenix Contact Co., Ltd.)
Recommend wire size:
0.3mm
2
 to 0.75mm
2
Wire the stripped wire after twisting it to prevent it from
becoming loose. In addition, do not solder it.
Wire Size (mm
2
)
Bar Terminal Model
Maker
with insulation sleeve
without insulation sleeve
0.3, 0.5
AI 0,5-10WH
Phoenix Contact Co.,Ltd.
0.75
AI 0,75-10GY
A 0,75-10
1
AI 1-10RD
A1-10
1.25, 1.5
AI 1,5-10BK
A1,5-10
0.75 (for two wires)
AI-TWIN 2 x 0,75-10GY
STF STR
PC
SD
RH
RM
RL
AM
C
B
A
10
2
5
4
RUN SE
S1 S2 SC
SO
SD
Wire stripping size
10mm
(0.39 inch)
Sleeve
Shell
Wi
re
0 to 0.5mm (0.02 inch)
Unstranded  
wires  
Damaged
Wires are not inserted 
into the shell
Crumpled tip